Company brief introduction
                 Company product
              Mianynag MSW Facility
      WSRLFJ Medical waste incinerator
        Resource Recovery and Utilization
                       Welcome To MianYang
                                    
                                      Return the home page
 
 
 
 

 

WSRLFJ Medical waste incinerator

Process Description

     Medical waste is conveyed automatically into the first chamber(830-9800C), drying and pyrolysis begin and follow the incineration, heat generated speeds up the  drying and incineration. Flue gas is then fully combusted in the second chamber(1050-11500C), full mixing and enough residence time is guaranteed in the third chamber(800-9800C) due to special shape and rotating air supply, flue gas is rapidly cooled going through the tube type heat exchanger, acid components are removed by semi dry process, fly dust is collected in bag filters and activated carbons are injected to absorb hazardous components before release into the air.

Incinerator body and feature

     The primary and secondary incinerators are divided into three compartments by refractory walls, carbon rich smoke is thermally oxidized in form of cyclone in the secondary and third chambers to ensure 3T in medical waste combustion, residues are removed from the bottom of the incinerator.

Specifications:

Residues thermal volume reduction:≤5%

Surface temperature:<50oC

Residence time:>2 seconds

Temperature:830-1150 oC

     Refer to report No.016,2004 issued by Sichuan Environment Protection Product Examination Center and  report No.003,2005 issued by National Environment Analysis and Test Center for pollutants test results.

Capacity:

50,100,200,300,500,750(kg/h)

    Output connection is reserved in the third chamber for heat or power generation.

    Examination with authenticate

    Flue gas is tested by National Environment Analysis and Test Center and  Sichuan Environment Protection Product Examination Center to be in compliance with GB19219-2003«Medical Waste Incinerator Technical Requirements»,the incineration system is approved by the experts examination organized by the Sichuan provincial EPA.

Medical Waste Incineration System Test Conclusions

    WSRLFJ-80 incinerator manufactured by Sichuan Science City Shengong Environment Protection Engineering Company and Mianyang Lidatong Technology Company is tested to be in compliance with the requirements stipulated in  GB19219-2003 «Medical Waste Incinerator Technical Requirements».

Dioxins Emission

    Based on GB18484-2001 «Hazardous Waste Incineration Pollution Control Standards ».

Results ( ngTEQ/m3 )

Item   sample1  sample2    average    standard

limit

Dioxin 0.34       0.31     0.33          0.5

Note:1feedstock: medical waste,capacity:2t/d;

 (2sample taken place: Mianyang Integrated Municipal Solid Waste Treatment Facility;

 (3sample volume:1.8379 m3 (sample1) and 1.7881 m3 (sample2)respectively under standard condition.